 Temperature Controller
A 96 x 96 mm (DIN) Controller for Control Valves
Controls motor valves without a potentiometer. Optimum PID control with feed-forward control circuitry. High precision regardless of the set temperature. Compatible with various inputs (input selected via internal switch). Models with communications capabilities also available.
E5AX-P
Ordering Information
Electronic Temperature Controller
Communications Model None RS-232C RS-422* RS-485* BCD Transmission output*/** (4 to 20 mA) E5AX-PRRF Communications Board Add-on Type E5AX-PRRM
E5AX-PRR
E5AX-PRR01
E5AX-PRR02 E5AX-PRR03 E5AX-PRR20
*The Controller can also be equipped with a terminal block to connect communications. Specify a terminal block by adding "-X" to the model number. Example: E5AX-PRR02-X **Capable of transmitting the process value or output value, but remote setting by external input is not possible.
Temperature Ranges
Input (switch selectable) K Chromel vs. alumel Range %C %F Resolution (%C/%F) (main settings and alarm) -200 to 1,300 -300 to 2,300 1 J/L Iron vs. constantan -100 to 850 -100 to 1,500 Thermocouple Temperature resistance thermometer R Platinum vs. platinum 13% rhodium 0 to 1,700 0 to 3,000 S Platinum vs. platinum 10% rhodium 0 to 1,700 0 to 3,000 PT platinum resistance thermometer (Pt100/JPt100) -99.9 to 450.0 -99.9 to 800.0 0.1
T/U Copper vs. constantan -200 to 400 -300 to 700
E Chromel vs. constantan 0 to 600 0 to 1,100
Communications Boards
Communications Model RS-232C E53-X01 RS-422 E53-X02 RS-485 E53-X03 BCD E53-X20 Transmission output (4 to 20 mA) E53-XF
1
E5AX-P
E5AX-P
Specifications
Ratings
Supply voltage Operating voltage range Power consumption Input Potentiometer input Control output Control mode Alarm output Setting method Indication method Other functions 100 to 240 VAC, 50/60 Hz (either frequency applicable with same unit) 85% to 110% of rated supply voltage Approx. 10 VA (at 100 VAC) to 15 VA (at 240 VAC) Approx. 12 VA (at 100 VAC) to 15 VA (at 240 VAC) with communication function Thermocouple (K/J/T/E/R/S/L/U) or platinum resistance thermometer (Pt100/JPt100) selectable 100 W to 2.5 kW Relay output: open, close; SPST-NO contacts; 3 A, 250 VAC (resistive load); inrush current: 1 A max. PID control with auto-tuning Relay output, SPST-NO contacts; 3 A, 250 VAC (resistive load) Digital setting via Up and Down Keys Digital indications (character heights PV: 15 mm and SV: 11 mm) (Color PV: red, SV: green) Upper and lower limits for set value Key protection Input shift Display unit selection (%C/%F) Normal and reverse output selection Valve position display Motor calibration function Watchdog timer function (Detects failures in the CPU and restores the CPU.) Manual output (balanceless-bumpless operation switchable)
Communications
Protocol Transmission method RS-232C, RS-422, RS-485 Half-duplex BCD Data select code Transmission output 4 to 20 mA DC Load: 600 W max. Resolution: Approx. 3,200 ---
Synchronization method Baud rate Transmission code Communications Write to Temperature Controller Read from Temperature Controller
Start-stop synchronization 150/300/600/1,200/2,400/4,800/9,600 bps ASCII (7-bit) Main setting, set alarm value, proportional band, integral time, derivative time, AT start/stop etc. Main setting, set alarm value, proportional band, integral time, derivative time, set limit value, process value, valve position, error codes, etc.
---
Main setting, set alarm value Main setting, set alarm value, process value, error codes, etc.
Write disabled
Process value (see note 3), valve position
Note:
1. The maximum total cable length must not exceed the following limits. RS-422: 500 m; RS-232C: 15 m; RS-485: 500 m 2. A maximum of 32 Temperature Controllers can be connected to one host computer using serial communications (RS-422, RS-485). 3. Outputs the temperature data within the set limits.
2
E5AX-P Characteristics
Setting accuracy Indication accuracy Disable band Proportional band Integral time Derivative time Alarm output setting range Alarm output hysteresis Sampling period Output refresh period Display refresh period Valve travel indication Full Open/close time Input shift Insulation resistance Dielectric strength Vibration resistance Shock resistance Life expectancy Ambient temperature Ambient humidity Memory protection Enclosure ratings (+0.3% of set value or +1%C, whichever greater), +1 digit max.
E5AX-P
(+0.3% of set value or +1%C, whichever greater), +1 digit max. (Set value coincides with the indicated value, because no relative error exists between both values.) 0.1% to 10.0% (in units of 0.1%) 0.1% to 999.9 %C/%F (in units of 0.1%C/%F) 1 to 3,999 s (in units of 1 s) 0 to 3,999 s (in units of 1 s) Thermocouple: -999% to 9,999%C/%F (in units of 1%C/%F) Platinum resistance thermometer: -99.9% to 999.9%C/%F (in units of 0.1%C/%F) 0.0% to 999.9 %C/%F (in units of 0.1%C/%F) 500 ms (temperature sensor input) 500 ms 500 ms (temperature sensor input) -99% to 999% (in units of 1%) 1 to 999 s ( in units of 1 s) Thermocouple: -999% to 9,999%C/%F (in units of 1%C/%F) Platinum resistance thermometer: -99.9% to 999.9%C/%F (in units of 0.1%C/%F) 20 MW min. (at 500 VDC) 2,000 VAC 50/60 Hz for 1 min between terminals of different polarities Malfunction: 2 to 55 Hz, 2G 10 min each in X, Y, and Z directions Destruction: 10 to 55 Hz, 0.75-mm double amplitude 2 hrs each in X, Y, and Z directions Malfunction: 200 m/s2 3 times each in 6 directions Destruction: 300 m/s2 3 times each in 6 directions Mechanical: 10,000,000 operations min. Electrical: 100,000 operations min. Operating: -10% to 55%C (with no icing) Storage: -25% to 65%C (with no icing) Operating: 35% to 85% Non-volatile memory Front panel: IEC standard IP50 Rear case: IEC standard IP20 Terminals: IEC standard IP00 Standard: Approx. 350 g; Communications: Approx. 480 g; Mounting bracket: Approx. 50 g
Weight
*The accuracy of U thermocouples under temperatures from -150% to 400%C (-240% to 700%F) is +2%C (+3.6%F) +1 digit. Accuracy is reduced below -150%C (-240%F). The accuracy of R and S thermocouples under 0% to 200%C (0% to 400%F) is +3%C (+5.4%F) +1 digit.
3
E5AX-P
E5AX-P
Nomenclature
Process Value (PV) Display Displays the process value, the character for parameter being displayed on the SV display and error messages. Auto-tuning Indicator Flashes on and off every second when auto-tuning is taking place. Manual Output Mode Indicator Lights when in manual output mode. Open Output Indicator Lights when the open output is ON. Close Output Indicator Lights when the close output is ON. Level Key Press for 2 seconds minimum to change levels to set different groups of parameters. Display Key Press to shift the display to the next parameter. Front Cover Down Key Press to decrease the main setting or other parameters. Successively decreases the value when held down.
Set Value (SV) Display Displays main setting and other parameters. Alarm Indicator Lights when the alarm output is ON. A/M Key (Automatic/Manual) Press for 1 second minimum to switch between auto output mode and manual output mode. Up Key Press to increase the main setting or other parameters. Successively increases the value when held down.
Operation
NOTICE:
Always turn off the power supply to the Electronic Temperature Controller before changing any switch settings.
Settings
1. Remove the internal mechanism from the housing. Lift the internal mechanism while pressing the hook at the bottom of the front panel. Protection switch (SW101, PROTECT)
Hook Pull out the internal mechanism while holding down the hook with your finger. 2. Four internal switches must be set on the E5AX: the temperature sensor selector, the operating mode selector, and the alarm mode selectors 1 and 2. The figures show the locations of these switches and the protection switches on the internal mechanisms. The protection switch can be used to disable key operation.
Alarm mode selector (SW205, ALM) Temperature sensor selector (SW206, INPUT) Operating mode selector (SW 201, FUNCTION)
Temperature Sensor Selector (SW206, INPUT)
This selector selects the temperature sensor to be used. It is factory-set to position 2 to designate a K-type (chromel-alumel thermocouple) temperature sensor. The following table lists the other pos-
4
E5AX-P
sible settings for temperature sensors. Refer to temperature range charts under Ordering Information for further information. The scale displayed (%C or %F) is selected by the operating mode selector (SW201).
E5AX-P Operating Mode Selector (SW201, FUNCTION)
This DIP switch selects the operation modes listed in the following table. Function Not used.* Control output Pin number 1 2 Pin setting Control setting
Leave turned OFF. ON OFF Normal (cooling) Reverse (heating) Enabled Disabled Enabled Disabled %F %C Enabled Disabled
Switch setting
Temperature sensor code
Temperature range %C %F 0 to 3,000 0 to 3,000 -300 to 2,300 -100 to 1,500 -300 to 700 0 to 1,100 -99.9 to 800.0 -99.9 to 800.0 -100 to 1,500 -300 to 700 PID display 6 SP (set point)** protection cancel Display unit 5 4 Input shift 3
ON OFF ON OFF ON OFF ON OFF
0 1 2 3 4 5 6 7 8 9
R S K J T E JPt100 Pt100 L U
0 to 1,700 0 to 1,700 -200 to 1,300 -100 to 850 -200 to 400 0 to 600 -99.9 to 450.0 -99.9 to 450.0 -100 to 850 -200 to 400
*Always operate with pin 1 OFF. Operating with pin 1 ON could result in malfunction. **SP protection cancel is effective only when SW101 (key protection) is on. If the SP protection cancel is ON, key protection (SW101 ON) will not apply to the set point, i.e., you will be able to change the set point regardless of the setting of SW101.
Alarm Mode Selector (SW205: ALM)
Alarm mode selector is provided on all E5AX Temperature Controllers. Alarm modes, listed in the following table, can be selected using this switch. The switch is factory-set to position 2, i.e., the upper-limit alarm mode. Switch setting 0 1 Mode (SW205) Alarm operation No alarm Upper- and lower-limit alarm Display No display Alarm output When X is positive OFF X X --When X is negative --Thermocouple: 0% to 9,999%C/%F Platinum resistance thermometer: 0% to 999.9%C/%F X Thermocouple: -999% to 9,999%C/%F X Platinum resistance thermometer: -99.9% to 999.9%C/%F Thermocouple: 9,999%C/%F 0% to Setting range
)--(
2
Upper-limit alarm
---( )--- -()- 3--e ---e 3--- 1--(
X X
X
3
Lower-limit alarm
4
Upper- and lower-limit range alarm Upper- and lower-limit alarm with standby sequence Upper-limit alarm with standby sequence Lower-limit alarm with standby sequence Absolute-value alarm
X
X
---
5
X
X
---
Platinum resistance thermometer: 0% to 999.9%C/%F X Thermocouple: -999% to 9,999%C/%F X Platinum resistance thermometer: -99.9% to 999.9%C/%F
6
X
7
8
Y 0%C
Y 0%C
5
E5AX-P Key Protection Switch (SW101, PROTECT)
E5AX-P
When the key protection switch is set to the ON position, the Level Key, Up and Down Keys, and Auto-tuning Key cannot be operated. In effect, the Temperature Controller is write-protected and the set values (such as the alarm value) can be read out only. The set point, however, will not be protected if the SP protection disable is turned ON (pin 4 of SW201).
6
E5AX-P Motor Calibration: calb
E5AX-P
The following setting are used to set the opening/closing time for controlling valves. Always set the following parameters when installing the controller. If a display is required for valve position, set the open and close positions at the same time. Down Keys to set the fully open/close time to a value between 1 and 999 s in the units of 1 s. PV sl-l 5. Press the Display Key. sl-l will be displayed and motor calibration will be complete. Press the Level Key for at least -200 Lower setting limit SV two seconds, confirm that in-t is displayed, and then press the Level Key again for at least two seconds to display the Press a. process value and return to the initial display mode. Settings with a Potentiometer (with Valve Position Display) 1. Turn on power and press the Level Key for at least two seconds. sl-l will be displayed. Then press the Display Key until calb is displayed. This is the initial mode when power is turned on for the first time. 2. Simultaneously press the Up and Down Keys for at least one second. fr-h will be displayed, the OPEN output will turn ON, and the valve will start to open. Press the Display Key as soon as the valve stops by the limit switch built into the motor. The count value for the fully open position will be set. 3. Press the Display Key. fr-l will be displayed, the OPEN output will turn OFF, the CLOSE output will turn ON, and the valve will start to close. Press the Display Key as soon as the valve stops by the limit switch built into the motor. The count value for the fully close position will be set. 4. Press the Display Key. mot will be displayed and the CLOSE output will turn OFF. The automatically set fully open/close time will be displayed. Use the Up and Down Keys to adjust the setting if required (value must be between 1 and 999 s in the units of 1 s). 5. Press the Display Key. sl-l will be displayed and motor calibration will be complete. Press the Level Key for at least two seconds, confirm that in-t is displayed, and then press the Level Key again for at least two seconds to display the process value and return to the initial display mode.
Press a.
calb
a
Motor calibration display Press the UP and Down keys simultaneously.
fr-l
Count value
Fully open position
Press a.
fr-l
Count value
Fully close position
Press a.
mot 30
Fully open/close time
WARNING
Settings when Not Using a Potentiometer (No Valve Position Display) 1. Turn on power and press the Level Key for at least two seconds. sl-l will be displayed. Then press the Display Key until calb is displayed. This is the initial mode when power is turned on for the first time. 2. Simultaneously press the Up and Down Keys for at least one second. fr-h will be displayed and the OPEN output will turn ON. 3. Press the Display Key. fr-l will be displayed, the OPEN output will turn OFF, and the CLOSE output will turn ON. 4. Press the Display Key. mot will be displayed and the CLOSE output will turn OFF. While mot is displayed, use the Up and Never calibrate the motor during control operation. Make sure that control operations have been stopped before calibrating. Note: 1. The output mode cannot be changed in motor calibration mode. 2. If the fully open position is less than the fully closed position, the value position will not be displayed and the display will show "a--- " for automatic and "m--- " for manual operation. If a potentiometer is not being used for feedback, press the Display Key at steps 2 and 3 without regarding the position of the valve and then set the fully open/close time. Here too, the display for value position will show "a--- " for automatic and "m--- " for manual operation.
7
E5AX-P Inputting Parameters
E5AX-P
The Temperature Controller has three display levels, 0, 1, and 2, in which only specific parameters can be set. Level 0 is the initial and is automatically entered at power application. To change the mode to set or change a different group of parameters, hold down the Level Key for 2 seconds minimum. The display level mode changes as shown below. Actual displays vary with models and switch settings. If a display does not appear as expected, check your switch settings.
-------
-------
Press the Level Key.
Press the Level Key.
-------
Power ON
Level 0
Level 1
Level 2 Press the Level Key.
Valve travel, main setting, alarm set value, input shift, PID constants
Lower/upper setting limit, alarm hysteresis, disable band, motor calibration, Fully open/close position, Fully open/close time
Input type, alarm mode
Level 0
Note:
PV
Process value SV
(Note 1) Valve travel
m0
Press a.
Process value
1. Not displayed in automatic output mode. "m--- " will be displayed if a potentiometer is not connected. 2. Not displayed in manual output mode. "a--- " will be displayed if a potentiometer is not connected. 3. Not displayed when the alarm is disabled (SW203 set to 0 or 9). 4. Not displayed when the input shift display is disabled (SW201, pin 3 OFF). 5. Not displayed when PID display is disabled (SW201, pin 6 OFF).
0
Press a. Process value
Main setting
Main Setting The set point can be changed with the Up and Down Keys. Valve Travel The value travel can be monitored. If a potentiometer is not connected, the display will show "a--- " for automatic and "m--- " for manual operation. While "m " is displayed in manual output mode, the Up Key will turn ON the OPEN output and the Down Key will turn ON the CLOSE output. Selecting the Output Mode The A/M Key can be pressed for one second or longer to change between the automatic and manual output modes. The balanceless-bumpless function will operate to prevent the output from changing abruptly. Automatic Output Mode In automatic output mode, the control will function automatically. When the A/M Key is pressed and the automatic output mode is first entered, displays like the following will appear (display level 0). PV SV
(Note 2) Valve travel
a0
Press a.
al 0
Press a.
(Note 3) Alarm value
in-5 0
Press a.
(Note 4) Input shift
p 40.0
Press a.
(Note 5) Proportional band
123 80
Process value Main setting
i 240
Press a.
(Note 5) Integral time
Manual Output Mode In manual output mode, the controller can be operated with the Up and Down Keys. The Up Key will turn the OPEN output ON and light the OPEN indicator. The Down Key will turn ON the CLOSE output and light the CLOSE indicator. When the A/M Key is pressed and the manual output mode is first entered, displays like the following will appear (display level 0). PV
d 40
Press a.
(Note 5)
123 m 80
Process value Valve position (%)
Derivative time SV
The MANU indicator will light and remain lit until the automatic output mode is returned to.
8
E5AX-P
Alarm: al When al is displayed on the PV display, the alarm value for alarm output can be set on the SV display. When the temperature exceeds or falls below the set alarm value, the corresponding alarm output is produced and the ALM indicator on the front panel lights. Usually, the alarm value is set as a deviation from the main setting, but it can also be set as an absolute value when the event alarm mode is selected. Set the alarm value by using the Up and Down Keys while al is displayed. The message is not displayed if the alarm mode selector is set to position 0. Factory-set to upper-limit, alarm value 0%C/%F Input Shift: in-5 When pin 3 of the operating mode selector switch (SW201) is set to the ON position, the input shift function can be used. This function is used to shift the temperature display from the measured value by a desired value, as shown by the examples in the following table: Input shift value 0 (without shift) 10 (shifted by 10%C) -10 (shifted by -10%C) Temperature measured by sensor 100%C 100%C 100%C Displayed temperature 100%C 110%C 90%C
E5AX-P
Level 1
PV SV
sl-l -200
Press a. Lower setting limit
sl-h 1300
Press a. Upper setting limit
hysa 0.2
Press a.
(Note 1) Alarm hysteresis
db 2.0
Press a. Disable band
This function can be used mainly for fine tuning compensation, while leaving the set temperature unaffected. Select this function by pressing the Display Key three times in display level 0. Proportional Band: p When the character p is displayed on the PV display, the proportional band (P constant) can be changed using the Up and Down Keys. The new value will be displayed on the SV display. It can be set in a range from 0.1% to 999.9%C/%F in units of 0.1%C/%F. The factory setting is 40.0%C/%F.
calb
Press a.
(Note 2) Motor calibration display
Press b r simultaneously.
fr-h
Count value
(Note 3) Fully open position
Press a.
NOTICE:
The output value will change according to the difference between the set value and the present value when the proportional band is changed during control operation. If this difference is too great, a drastic change will result. Always switch to the manual output mode before changing the proportional band.
fr-l
Count value
Fully closed position
Press a.
Integral Time (Reset Time): i When the character i is displayed on the PV display, the integral time (I constant) can be changed using the Up and Down Keys. It can be set in a range from 0 to 3,999 seconds in units of 1 second. The factory setting is 240 seconds. Derivative Time (Rate Time): d The derivative time (D constant) can be changed when the character d is displayed on the PV display using the Up and Down Keys. It can be set in a range from 0 to 3,999 seconds in units of 1 second. The factory setting is 40 seconds.
mot 30
Press a. Note: 1. Not displayed when the alarm is disabled (SW205 set to 0 or 9). 2. Motor calibration will be displayed when power is turned on for the first time. 3. Displayed only when the motor calibration mode is entered. Fully open/close time
9
E5AX-P
Lower/Upper Limits of Setting Range: sl-l, sl-h -200 0 400 1,300
E5AX-P
Input Type: in-t When in-t is displayed on the PV display, the present setting of the input type selector (SW206), is displayed on the SV display. The following table shows the messages that may be displayed: Display SL-L SL-H Sensor R S K J T E JPt100* Pt100** L U
r pr
Basically, the temperature range that can be measured is determined by the temperature sensor to be used. For example, when a K-type (chromel-alumel thermocouple) temperature sensor is selected, the measurable range is from -200%C to 1,300%C. However, this temperature range can be narrowed, for example, to 0%C to 400%C. To do this, set the lower-limit value of the temperature setting range, in this case to 0%C, on the SV display by using the Up and Down Keys while 5l-l is displayed on the PV display. Similarly, set the upper-limit value, 400%C, while 5l-h is displayed. If the process temperature falls below the set lower-limit value or exceeds the set upper-limit value, it is displayed on the PV display within the temperature range of the temperature sensor. Hysteresis Alarm: hysa The hysteresis alarm value for the alarm can be set in a range from 0.0% to 999.9%C while hysa is displayed on the PV display using the Up and Down Keys. The factory setting is 0.2%C/%F. Disable band: db The disable band can be set in a range from 0.1% to 10.0% while db is displayed on the PV display using Up and Down Keys. The factory setting is 2.0%. Motor Calibration: calb Designate whether or not to perform motor calibration. To enter the mode, simultaneously press the Up and Down Keys for at least one second. Press the Display Key to return to sl-l.
5 pr k ca j ic t cc e cr jpt pt l ic u cc
*Meets JIS 1981. **Meets JIS 1989, DIN. AL (Alarm Mode): al
WARNING
Never calibrate the motor during control operation. Make sure that control operations have been stopped before calibrating. fr-h Fully open position fr-l Fully closed position mot Opening/closing time The motor is calibrated. Refer to page 9.
When al is displayed on the PV display in level 2, alarm output mode or the present setting of the corresponding alarm mode selector (SW205) is displayed on the SV display. The following table shows the messages that may be displayed. Display No display Alarm mode No alarm Upper- and lower-limit alarm Upper-limit alarm Lower-limit alarm Upper- and lower-limit range alarm Upper- and lower-limit alarms with standby sequence Upper-limit alarm with standby sequence Lower-limit alarm with standby sequence Absolute-value alarm
)--( ---( )--- -()- 3--e ---e 3---
Level 2
In level 2, selected input sensor, and modes for alarm output can be monitored. Note that level 2 is a monitoring level only and thus no parameters can be changed. When the Level Key is pressed for 2 seconds minimum after power application, 5l-l is displayed on the PV display. Hold down the Level Key again for 2 seconds minimum to display o on the PV display. Then, selected input sensor, and alarm modes can be monitored each time the Display Key is pressed.
in-t k ca
Press a. Input type
1--c
al ---(
Press a. Alarm mode
10
E5AX-P Starting Control Operation
The E5AX will start control operations as soon as power is turned on until power is turned off. If you don't want control operations to be performed while setting parameters, turn off the power and then turn it back on after setting the desired parameters. Previous PID constants Main setting
E5AX-P
New PID constants
Auto-tuning
When the Level Key and Mode Key are pressed at the same time for 1 second minimum, the Temperature Controller automatically starts tuning the PID constants. While auto-tuning is in operation, the auto-tuning indicator on the front panel will flash. The Temperature Controller executes control based on the set PID constants (factory set to P = 40%C, I = 240 seconds, and D = 40 seconds) until the temperature of the controlled system reaches the set temperature. After that, the Temperature Controller automatically adjusts the PID constants using the limit cycle method. When the auto-tuning indicator turns off, the auto-tuning is terminated and PID constants are renewed.
AT indicator flashes Limit Cycle Method: the optimum PID constants are calculated by this method by varing the control output variable and generating external oscillation. Auto-tuning can be carried out regardless of whether the Temperature Controller is performing reverse (heating) or normal (cooling) operation. To stop auto-tuning, hold down the Level Key and Mode Key again simultaneously for 1 second minimum. All settings will return to those prior to the beginning of auto-tuning. Automatic tuning can be executed at any time: at power application, while the temperature is rising, or after the control action has stabilized.
Error Messages
The Temperature Controller is provided with self-diagnostic functions, and will display an error message on the PV display when an error is detected. Message Cause Control output Normal Reverse Open: ON Close: OFF Open: OFF Close: ON Open: ON Close: OFF Sends alarm signal in accordance with the set alarm mode. Sends alarm signal in accordance with the set alarm mode. Sends alarm signal in accordance with the set alarm mode. Proportional alarm output is OFF, however. OFF Alarm output
ffff ---- 5.err (flashes)
Input temperature has exceeded the upper limit of the temperature range by more than 20%C. Input temperature has fallen below the lower limit of the temperature range by more than 20%C.* The thermocouple has burned out or short-circuit bar has been removed. The platinum resistance thermometer has burned out or A and B terminals have been short-circuited. Memory failure (e111) or A/D converter failure (e333) has occurred. Temperature Controller must be repaired if recovery is not made by turning power off once and on again.
Open: OFF Close: ON Open: ON Close: OFF Open: OFF Close: ON
e111 (flashes) e333 (flashes)
Open: OFF Close: OFF
Open: OFF Close: OFF
*When the temperature resistance thermometer is used, this message is displayed when the temperature has fallen below -99.9%C.
11
E5AX-P
E5AX-P
Dimensions
Note: All units are in millimeters unless otherwise indicated.
_96 12 89 11 5
Mounting Screw
2 to 10
RS-422 RS-485 RDB RDA SG SDA SDB 4 to 20 mA transmission output SG
Communications connector Communications board Communications board (RS-232C and BCD connector is shown.) (RS-422 and 485 terminals are shown.) (4 to 20 mA transmission output is shown.) Panel Cutout Side-by-side Mounting of N Controllers
92 0
+0.8
L 92 +0.8 0
+0.8
92 0
120 min.
L = (96N - 3.5)+1 0
Installation
Control Open output Close
Ground FG terminal 18 under noise-interfered environment. 100 to 240 VAC, 50/60 Hz
Alarm output
Use these terminals when connecting a platinum resistance thermometer (remove short bar from terminals 14 and 15).
Potentiometer input (see Note 1) Use these terminals when connecting a thermocouple (do not remove short bar from terminals 14 and 15).
Note:
1. Connect a valve position indicator if required. 2. Do not connect unused terminals.
12
E5AX-P
E5AX-P
Precautions
Mounting
The dimensions of the Temperature Controller conform to DIN 43700. Recommended panel thickness is 1 to 8 mm. Do not install the Temperature Controller in a location exposed to excessive dust or corrosive gases. Moreover, avoid locations subject to heavy vibration or shock, water or oil spray, or high temperatures. Any of these condition will affect product life. Isolate the Temperature Controller from equipment that generates strong, high-frequency noises such as high-frequency welders, because such equipment may prevent proper operation. Attach the two mounting brackets supplied with E5AX on the top and bottom of the Temperature Controller. Tighten the screws of the mounting brackets with your fingers.
Mounting bracket
Stickers Inside Frontcover
Stickers indicating the temperature sensor type (R, S, K, J, T, E, L, and U) are supplied with the Temperature Controller. Attach the proper stickers to the front panel as shown below.
Sticker identifying input type
Connection Examples
With Solderless Terminal Use M3.5 solderless terminals with the Temperature Controller's M3.5 self-rising pressure plate screws. Solder-dipped Leads Strip 6 to 12 mm of the lead wires and carefully arrange the wire tips. Do not tighten the terminal screw with excessive force, because doing so may damage them. The terminal block of the Temperature Controller is constructed so that the lead wires can be connected to all the terminals from the same direction. Top
Bottom
Input Connection
To reduce inductive noise influence, the lead wires connecting the input to the Temperature Controller must be separated from the power lines and load lines. Use the specified compensating conductors for thermocouples. When using a thermocouple as the temperature sensor, attach the short-circuit bar shown in the terminal block diagram on the housing. Use lead wires having a small resistance for temperature resistance thermometers. Be sure to remove the short-circuit bar from the terminals when a temperature resistance thermometer is used. Sequenced Circuits Several seconds are required until the relay in turned ON after power has been supplied to the Temperature Controller. Therefore, take this time delay into consideration when designing sequenced circuits which incorporate a Temperature Controller.
13
E5AX-P
E5AX-P
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. H54-E1-1A
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Temperature Control Devices Division 29th Fl., Crystal Tower Bldg. 1-2-27, Shiromi, Chuo-ku, Osaka 540 Japan Phone: 06-949-6070 Fax: 06-949-6084 Printed in Japan 0791-1M
14


▲Up To Search▲   

 
Price & Availability of E5AX-PRRM

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X